TY - GEN
T1 - Long term voltage stability thevenin index using voltage locus method
AU - Matavalam, Amarsagar Reddy Ramapuram
AU - Ajjarapu, Venkataramana
N1 - Publisher Copyright: © 2014 IEEE.
PY - 2014/10/29
Y1 - 2014/10/29
N2 - Monitoring long term voltage stability of the power grid is necessary to ensure the secure operation of the system. In this paper, the voltage locus of the load phasor as a function of the load increase is studied is studied from a geometric perspective. This locus is used to propose a Voltage Stability Index based on the magnitude of the measured voltage and calculated thevenin equivalent angles. A novel method to calculate only the necessary thevenin parameters is presented. The proposed Voltage Stability Index and the efficient thevenin calculation method are tested on the IEEE-30 Bus system with lagging, unity and leading power factors.
AB - Monitoring long term voltage stability of the power grid is necessary to ensure the secure operation of the system. In this paper, the voltage locus of the load phasor as a function of the load increase is studied is studied from a geometric perspective. This locus is used to propose a Voltage Stability Index based on the magnitude of the measured voltage and calculated thevenin equivalent angles. A novel method to calculate only the necessary thevenin parameters is presented. The proposed Voltage Stability Index and the efficient thevenin calculation method are tested on the IEEE-30 Bus system with lagging, unity and leading power factors.
KW - Long term voltage stability
KW - Maximum power transfer
KW - Thevenin equivalent
KW - Voltage locus
KW - Voltage stability index
UR - https://www.scopus.com/pages/publications/84930986712
UR - https://www.scopus.com/pages/publications/84930986712#tab=citedBy
U2 - 10.1109/PESGM.2014.6938912
DO - 10.1109/PESGM.2014.6938912
M3 - Conference contribution
T3 - IEEE Power and Energy Society General Meeting
BT - 2014 IEEE PES General Meeting / Conference and Exposition
PB - IEEE Computer Society
T2 - 2014 IEEE Power and Energy Society General Meeting
Y2 - 27 July 2014 through 31 July 2014
ER -